PANEL-MOUNT DIGITAL TEMPERATURE INDICATOR


 

 

 

UM330/UM350 - Digital Indicators with Alarms


um350

  • Parameter Setting Display:
    • Displays parameter item and setpoint.

  • PV Display:
    • Displays measured input value (PV) and error code in error occurrence.

    • Alarm Indicator lamps (AL1 to AL4).




 

UM330/350 Specification Table
UM330
UM350
PV/Parameter Data Display:
4 digits / 4 digits
PV Input:
1 universal input (TCs, RTDs, mV, V)
Indication Accuracy:
0.1% +/-1 digit
Control Scan Period:
250ms
Analog Output (4 to 20 mA):
1 point (Cannot use with LPS15V)
Loop Power Supply (LPS):
2 points, 15V and 24V (option)
Digital Inputs:
1
Digital Alarm Outputs:
3
RS-485 Communication Protocols:
Four-wire, MODBUS, PC-link, Ladder
Approvals:
General = UL, CE, CSA / Front Protection = IP55
Power Supply, Consumption:
90 to 264 V AC, max. 20VA
Size, Weight:
96(W)*48(H)*100(D)mm, 1 kg 96(W)*96(H)*100(D)mm, 1 kg
Ambient T, Limits RH
0 to 50 °C, 20 to 90%RH

 

Model and Suffix Codes
Model
Suffix Code
Description
UM330
Digital Indicator with alarms
Type
-0
Standard Type
-3
Standard type with 24 V DC loop power supply
Options
0
None
1
Communication functions, 1 additional alarm
2
1 additional alarm
Model and Suffix Codes
Model
Suffix Code
Description
UM350
Digital Indicator with alarms
Type
-0
Standard Type
-3
Standard type with 24 V DC loop power supply
Options
0
None
1
Communication functions, 1 additional alarm
2
1 additional alarm

 

If you have any questions regarding Marlin Instruments,
Please call us at 1-800-321-6648 or e-mail us at marlincle@marlinmfg.com

 

 
Go to top of page

Marlin Manufacturing Corporation · 12800 Corporate Drive · Parma · Ohio · 44130

Phone: (216) 676-1340 or (800) 321-6648·
Fax: (216) 676-1344 · Email: marlincle@marlinmfg.com
Company Profile Contact Us Home Home

Copyright 2003 Marlin Mfg. Corporation. All Rights Reserved.

Site Design: tlhalfacre@ameritech.net & Abstract Productions