INDICATING CONTROLLERS


 




ut450

  • UT350/UT450/UT550 - Digital Indicating Controllers


  • 96x96 (1/4DIN) Controllers

  • 1 Universal Input (TCs, RTDs, mV, V)

  • 0.1% +/- 1 digit Accuracy



 

UT350/450/550 Specification Table
UT350
UT450
UT550
PV/SP Data Display:
4 digits / 4 digits
5 digits / 5 digits
PV Input:
1 universal input (TCs, RTDs, mV, V)
Indication Accuracy:
0.1% +/- 1 digit
Auxilliary Analog Input:
Not Available
1 for Rermote SP
1 for Remote SP or Secondary PV
Control Scan Period:
250 ms
200ms
50, 100, 200ms
Control Loops:
1
1
1 or 2 (cascade)
Control Modes:
MAN/AUTO
MAN/AUTO/CAS, RUN/STOP
Number of Setpoint (SP):
4
8
Control Algorithm:
ON/OFF, Time-Proportional PID,
Continuous PID,
Heating & Cooling
ON/OFF, 3 position, Time-Proportional PID, Continuous PID,
Heating & Cooling
SUPER, Auto Tunings:
SUPER, SUPER2, AT
Control Outputs (MV):
Select from Relay, Voltage Pulse or 4 to 20 mA
Auxilliary Analog Output
(4 to 20 mA):
1 point except for Heating/Cooling control
(Cannot use with LPS15V)
1 point (Cannot use with LPS15V)
2 points when MV is relay output
Loop Power Supply (LPS):
2 points, 15V and 24V(option)
Digital Inputs :
2
2, 3, 6 or 7
2, 3, 7 or 8
Digital Outputs:
3
3 or 4
3 or 7
RS485 Communicatiopn Protocols:
Four-wire, Protocol is MODBUS, PC-link, Ladder or Coordinated Operation
Approvals:
General = UL, CE, CSA / Front Protection = IP55
Other Specifications:
Size=96(W)96(H)*100(D)mm, Power Supply=90 to 264V AC, Power Consumption = max. 20VA
Ambient T, Limits RH:
0 to 50 °C, 20 to 90% RH

 

Model and Suffix Codes
Model
Suffix Code
Description
Notes
UT350

Digital Indicating Controller

NOTE: Sensor of heater burnout alarm is CTL-6-S or CTL-12-S36-8 (URD Co., Ltd., Japan) To be purchased separately.
Type
-0
Standard Type
-2
Heating/Cooling Type
-3
Standard type with 24V DC loop power supply
Options
-0
None
-1
Communication functions, heater burnout alarm (2 points) Note
-2
Heater burnout alarm (2 ponts) Note
Model and Suffix Codes
Model
Suffix Code
Description
Contact Input/Output Available
UT450

Digital Indicating Controller

Contact Input
Contact Output
Type
-0
Standard Type
-1
Position-proportional type
-2
Heating/Cooling type
-3
Standard type with 24V DC loop power supply
-4
Position-poroportional type with 24V DC loop power supply
Options
-0
None
Dl1, Dl2
AL1, AL2, AL3
-1
Communication functions, remote input, 5additional Dls, 1 additional Alarm
Dl1 to Dl6, R/L
AL1 to AL4
-2
Communication functions, remote input, 1additional Dls
Dl1, Dl2, R/L
AL1, AL2, AL3
-3
4 additional Dls, 1 additional Alarm
Dl1 to Dl6
AL1 to AL4
-4
Remote Input, 1additional Dls
Dl1, Dl2, R/L
AL1, AL2, AL3
Model and Suffix Codes
Model
Suffix Code
Description
Contact Input/Output Available
UT550

Digital Indicating Controller

Contact Input
Contact Output
Type
-0
Standard Type
-1
Position-proportional type
-2
Heating/Cooling type
-3
Standard type with 24V DC loop power supply
-4
Position-poroportional type with 24V DC loop power supply
Options
-0
None
Dl1, Dl2
DO1, DO2, DO3
-1
Communication functions, auxilliary analog(remote) input,
6 additional Dls, 4 additional DOs
Dl1 to Dl8
DO1 to DO7
-2
Communication functions, auxilliary analog (remote) input, 1 additional Dls
Dl1, Dl2, Dl8
DO1, DO2, DO3
-3
5 additional Dls, 4additional DOs
Dl1 to Dl7
DO1 to DO7
-4
Auxilliary analog (remote) input, 1 additional Dl
Dl1, Dl2, Dl8
DO1, DO2, DO3

 

If you have any questions regarding Marlin Instruments,
Please call us at 1-800-321-6648 or e-mail us at marlincle@marlinmfg.com

 

 
Go to top of page

Marlin Manufacturing Corporation · 12800 Corporate Drive · Parma · Ohio · 44130

Phone: (216) 676-1340 or (800) 321-6648·
Fax: (216) 676-1344 · Email: marlincle@marlinmfg.com
Company Profile Contact Us Home Home

Copyright 2003 Marlin Mfg. Corporation. All Rights Reserved.

Site Design: tlhalfacre@ameritech.net & Abstract Productions